One RS-232 serial port with RJ45 connector for initial switch setup (if not using EZSwitch Setup) and
factory default restoration. (the integral LEDs remain unlit at all times)
A USB port that provides storage for firmware updates, output of the supportSave command and
storage for configuration uploads and downloads.
Two hot-swappable, redundant power supply and fan FRUs. There are two fans per FRU.
Rack-mount design (1U form factor) in a 19-inch EIA rack.
One LED (green/amber) per FC port to indicate status.
One LED (green) for system power.
One LED (green/amber) for system status.
Two Ethernet LEDs (integrated with RJ45) for speed and activity status.
SEEPROM for switch identification.
Voltage monitoring.
Fan monitoring including flow direction.
Temperature monitoring.
Real-time clock (RTC) with battery.
The Brocade EZSwitchSetup wizard that makes SAN configuration a three-step point-and-click task.
Facility requirements
The following table provides the facilities requirements that must be met for the Brocade 6510.
Facility Requirements TABLE 1
Type Requirements
Electrical Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating on the
switch nameplate
Circuit protected by a circuit breaker and grounded in accordance with local electrical codes
Refer to Brocade 6510 Technical Specifications on page 0 for complete power supply
specifications.
Thermal A minimum air flow of 79.8 cubic meters/hour (47 cubic ft/min.) available in the immediate
vicinity of the switch.
NOTE
Although this airflow may exceed the airflow maximum listed in the device Technical
Specifications, the additional airflow is recommended to pressurize the inlet (cool isle) side of
rack installations relative to the exhaust side to minimize recirculation of hot air back to the inlet
side.
Ambient air temperature not exceeding 40 ° C (104 ° F) while the switch is operating
Rack (when
rack-mounted)
One rack unit (1U) in a 48.3 cm (19-inch) rack - must use rack kits designed for the extra width
of the Brocade 6510 switch to mount in standard racks
All equipment in rack grounded through a reliable branch circuit connection
Additional weight of switch not to exceed the rack’s weight limits
Rack secured to ensure stability in case of unexpected movement
Facility requirements