Brocade ServerIron ADX Installation Guide 17
53-1003445-01
Installation precautions
2
Lifting precautions
Make sure the rack or cabinet housing the device is adequately secured to prevent it from
becoming unstable or falling over.
Mount the devices you install in a rack or cabinet as low as possible. Place the heaviest device at
the bottom and progressively place lighter devices above.
Power precautions
Use a separate branch circuit for each AC power cord, which provides redundancy in case one of
the circuits fails.
Ensure that the device does not overload the power circuits, wiring, and over-current protection.
To determine the possibility of overloading the supply circuits, add the ampere (amp) ratings of all
devices installed on the same circuit as the device. Compare this total with the rating limit for the
circuit. The maximum ampere ratings are usually printed on the devices near the input power
connectors.
High Touch Current: Earth connection essential before connecting supply (ServerIron ADX 4000,
8000, 10000).
Disconnect the power cord from all power sources to completely remove power from the device.
Make sure to choose the appropriate circuit device, depending on the number of AC power
supplies installed in the chassis.