Brocade ServerIron ADX Installation Guide 61
53-1003445-01
Replacing a Fan Tray
2
Replacing a Fan Tray
You can replace the fan tray in the ServerIron ADX chassis.
NOTE
Fan trays are hot swappable. Hot swapping fan trays should be done within 5 minutes so the unit
will continue to function correctly without any fans. However, Brocade recommends that you
disconnect the power supply from AC or DC power before installing or removing the fan tray.
Replacing the ServerIron ADX 1000 or
ServerIron ADX 1000F Fan Tray
To replace the ServerIron ADX 1000 fan tray, follow these steps.
1. Power down and unplug the chassis.
2. Unscrew the two screws that secure the fan tray to the chassis (Figure 42).
FIGURE 42 Replacing the ServerIron ADX 1000 Fan Tray
3. Slide the fan tray out.
4. Slide the new fan tray in and tighten the screws to secure it to the chassis.
5. Plug the chassis back in and power up.
Replacing the ServerIron ADX 4000 or
ServerIron ADX 8000 Fan Tray
To replace the ServerIron ADX 4000 or ServerIron ADX 8000 fan tray, follow these steps.
1. Power down and unplug the chassis.
2. Pull the thumb-lever on the power supply down and pull the fan-tray out by the handle
(Figure 43).
3. Slide the new fan-tray in until it is secure in the chassis.