NEBS installation requirements (Continued)TABLE 4
Reference Warning, requirement, or statement
Bonding of Battery
Return (BR) Input
Terminals
The battery returns of the Brocade device must be connected (DC-I).
Connections The Brocade device must be grounded via a copper ground conductor.
Connections All bare grounding connection points to the Brocade device must be cleaned and
coated with an antioxidant solution before connections are made.
Connections All surfaces on the Brocade device that are un-plated must be brought to a bright finish
and treated with an antioxidant solution before connections are made.
Connections All non-conductive surfaces on the this device must be removed from all threads and
connection points to ensure electrical continuity.
Connections The Brocade VDX 8770 utilizes a two-hole compression type, agency-approved
crimped connector with a copper #2 American Wire Gauge (AWG) that utilizes 20 inch
pounds of torque to secure it to the frame and EUT.
Input DC Voltage The Brocade VDX 8770 is capable of operating at 200-240 V, 50/60 Hz at a maximum
current level of 16.0 A max., or -48VDC, 70.0 A max. per power supply.
Thermal policy Due to recent changes in the NEBS thermal policy testing procedures, Brocade has
made changes to the thermal policy for the Brocade VDX 8770. These changes include
an additional fan speed (raising the number of fan speeds to 4 from 5) and slightly
altered trigger temperatures. Additional non-user visible RASlog message generation
has also been included with this change to allow for easier debugging and thermal
history recording.
The precise values for temperature and fan RPM are related to the specific hardware
combinations possible in the modular switch. For the sake of brevity, the following table
lists the possible range of values for each heat level.
NEBS thermal policy levels TABLE 5
Level Description Ambient temperature Temperature RPM
1 LOW up to 25C up to70C 2500 RPM
2 MED-LOW up to 25C from 48C through
80C
3500 RPM
3 MED up to 39C from 52C through
86C
5500 RPM
4 HIGH up to 51C from 65C through
93C
7350 RPM
5 MAX up to 58C from 73C through
99C
9300 RPM