CAUTION
All devices with DC power supplies are intended for installation in restricted access areas only.
A restricted access area is where access can be gained only by service personnel through the
use of a special tool, lock and key, or other means of security, and is controlled by the authority
responsible for the location.
CAUTION
For the DC input circuit, (DC power supply part number RPS9-DC), make sure there is a 20-amp
circuit breaker, minimum -48VDC, double pole, on the input to the terminal block. The input
wiring for connection to the product should be copper wire, 12 AWG, marked VW-1, and rated 90
degrees Celsius.
CAUTION
For a DC system, use a grounding wire of at least 6 American Wire Gauge (AWG). The 6 AWG
wire should be attached to an agency-approved crimp connector crimped with the proper tool.
The crimp connector should allow for securement to both ground screws on the enclosure. For
the Ground lug, use UL listed Panduit crimp connector, P/N LCD6-10A, and two 10-32, PPH,
screws to secure crimp connector to chassis. Grounding position is located on the side of the
chassis adjacent ground symbol.
Installation site preparation
Cabling infrastructure
Ensure that the proper cabling is installed in the site. Refer to Cabling infrastructure or
www.brocade.com for a summary of supported cabling types and their specifications.
DANGER
The intra-building port or ports of the equipment or subassembly is suitable for connection to
intra-building or unexposed wiring or cabling only. The intra-building port or ports of the
equipment or subassembly MUST NOT be metallically connected to interfaces that connect to
the outside plant (OSP) or its wiring. These interfaces are designed for use as intra-building
interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 5) and require
isolation from the exposed OSP cabling. The addition of Primary Protectors is not sufficient
protection in order to connect these interfaces metallically to OSP wiring.
Installation location
Before installing the device, plan its location and orientation relative to other devices and equipment.
Allow at least 3 in. of space at the front of the device for the twisted-pair, fiber-optic, and power cabling.
Also, allow a minimum of 3 in. of space between the sides and the back of the device and walls or other
obstructions.
A Brocade device is suitable for installation in Network Telecommunications facilities and locations
where the NEC (National Electric Code) apply.
The device must be installed in a restricted access location, either a Central Office or customer-
premises equipment location.
Installation site preparation
Brocade NetIron CES 2000 Series and NetIron CER 2000 Series Hardware Installation Guide 49
53-1003263-02